CLEAN ROOM DESIGN CRITERIA
Criteria
Class Limits

10
100
1000
10000
100000
Air Changes Per Hour
600
300 – 480
150 - 250
60 – 120
10 - 40
Hepa Filter Coverage %
100
70 – 100%
30 – 60%
10 – 30%
5 – 10%
CFM PerSQ/FT
90
65-36
32-18
16-9
8-5
Typical Filter Velocity
99,9997
99,997
99,997
99,997
99,97
Typical Velocity Filter
60 – 110 FPM
50 -  90 FPM
40 – 90 FPM
25 – 40 FPM
10 – 30 FPM
Air Flow Type
Unidirectional
Unidirectional
Mixed
Mixed
Mixed
Typical Return Air System
Raised Floor
Low Wall
Low Wall
Low Wall & Ceiling
Low Wall & Ceiling