CLEAN ROOM
DESIGN CRITERIA
|
|||||
Criteria
|
Class Limits
|
||||
|
10
|
100
|
1000
|
10000
|
100000
|
Air Changes Per
Hour
|
600
|
300 – 480
|
150 - 250
|
60 – 120
|
10 - 40
|
Hepa Filter
Coverage %
|
100
|
70 – 100%
|
30 – 60%
|
10 – 30%
|
5 – 10%
|
CFM PerSQ/FT
|
90
|
65-36
|
32-18
|
16-9
|
8-5
|
Typical Filter
Velocity
|
99,9997
|
99,997
|
99,997
|
99,997
|
99,97
|
Typical Velocity
Filter
|
60 – 110 FPM
|
50 -
90 FPM
|
40 – 90 FPM
|
25 – 40 FPM
|
10 – 30 FPM
|
Air Flow Type
|
Unidirectional
|
Unidirectional
|
Mixed
|
Mixed
|
Mixed
|
Typical Return
Air System
|
Raised Floor
|
Low Wall
|
Low Wall
|
Low Wall & Ceiling
|
Low Wall & Ceiling
|
Home
»
CLEAN ROOM DESIGN CRITERIA
»
CLEAN ROOM DESIGN CRITERIA
0 comments :
Post a Comment